HIGHLOGO 2-910 | Jung Pumpen

HIGHLOGO 2-910

JP48001
Mechanical data
Type
Duplex units without level control
HxWxL[mm]
275 x 250 x 155
Weight
4 kg
Extension for accessory
optinoal
Main switch
optinoal
Electrical data
Voltage
3/N/PE~400 V
Motor protection
6.3 ... 10 A
Pre-fuse
25 A
Type of enclosure
IP 44
Alarm buzzer
Yes
Connection 9V battery
Yes
Connection thermal contact
Yes
Connection dry run protection
Yes
Display operation hours/switching cycles
Yes
Display amps
Yes
Automatic alternate operation
Yes
Digital signal contact
optinoal
Input AUX
Yes
Event memory
Yes
Integrated GSM-Modem
optinoal
Max. switching power
5,5 kW
Motor protection typ
Motor protection switch
Peak load operation
Yes
Start
direct
Fault contact 230 V
Yes
Fault contact pot. Free
2 changeover contacts, 5A
Accessories BmG/immersion sensor
Electrical accessory
Code No.
a
Rechargeable battery
9 V, for mains independent alarm JP44850
b
Level control
Subm. switch pack B 3 subm. ball contact switch with 9.5 m and fixing devices JP16725
Subm. switch pack BmG 3 subm. ball contact switch with 9.5 m and counterweight JP16726
Submersible switch pack BHmG Submersible ball contact switch 9.5 m with counterweight JP24769
Auxiliary switch unit ExH-B for explosion-proof pumps only for ex-proof pumps only (duplex units) JP00295
Submersible probe (10 m) for analogue water level indicator (4-20 mA) JP44808
Weight to stabilize the subm. ball contact switch JP44803
Smart Home
FTJP radio transmitter JP47209
c
Pre-mounted level control
Dry run protection (10 m) for ex-proof systems, mounted JP44807
Pressure sensor set (10 m) for analogue water level display with tube set JP26187
Pressure switch (10 m) with pressure sensor and tube set JP26196
Submersible probe Ex (10 m) for analogue level indicator, housing extension required JP44809
d
Pre-mounted accessory
GSM battery fpr HighLogo 2 12V, for duplex units, factory fitted incl. housing extension JP49357
Main switch 15 kW, factory fitted only JP48002
Modem GSM for HighLogo factory fitted, incl. flat antenna JP49356
Parametrization GSM modul pre-setting for customer demand JP55202
e
Retrofittable accessory
CEE-Plug 32 A 1.5 m cable JP50817
Modem GSM for HighLogo retrofit unit incl. GSM antenna JP50444
Battery 12V with housing retrofit unit for independent modem operation JP50635